The following parameters can be set in the 'ABULiner' parameter level of the LIS-SV.
|
Parameter |
Designation |
See |
|
5.10 |
Calling up the parameter level |
|
|
5.11 |
Activating the LIS-SV for the ABULiner |
|
|
5.11 |
Setting the gear ratio |
|
|
5.12 |
Activating double lifting speed |
|
|
5.14 |
Setting the run-on time of the auxiliary fan |
|
|
Danger during setting work! During setting work on the LIS-SV, monitoring of the wire rope hoist is switched off. This means the wire rope hoist cannot be monitored for excess load, among other things. This means the wire rope hoist cannot be monitored for excess load, among other things. This in turn means the load could fall and kill or injure people! Do not use the crane for normal work during setting work, and only lift loads very carefully for test purposes! |
All LIS-SV parameters which are important for the ABULiner are combined in a separate parameter level, which is shown as a submenu.
|
|
Move the load hook out of
the limit switch range (up or down).
During parameter setting, the load hook must not be within the limit switch range.
Open the menu of the
LIS-SV. See the documentation “Load indicator system LIS-SV”.
|
| |
|
Enter button |
Arrow buttons |
Select parameter 5.10.
Press ENTER.
● The 'ABULiner' parameter level is activated.
● Parameter 5.11 is displayed.
|
| |
|
Enter button |
Arrow buttons |
Select parameter 5.99.
Press ENTER.
● The previous parameter level is reactivated.
● Parameter 5.10 is displayed.
The LIS-SV is automatically activated for the ABULiner if a value is entered for the parameter 5.11.
In the ABULiner mode (a value is set for parameter 5.11):
─ The LIS-SV can monitor the total load for a maximum of two wire rope hoists.
─ Input F3 (normally used for measuring the load of wire rope hoist 3) now serves in monitoring the current rotational frequency of the hoist motor.
─ A value can be entered for parameter 3.0 (maximum load capacity of wire rope hoist 3). If a value is entered for this, parameter 5.11 cannot be set.
─ This interlocking thus excludes an incorrect setting.
─ The load-controlled switching point at output TxD of the LIS-SV cannot be used.
─ Parameter 4.5 (setting for load-controlled switching point) is not available.
In the normal mode (no value is set for parameter 5.11):
─ Operation of the ABULiner Lifting/Lowering unit is not possible.
─ The LIS-SV can monitor the total load for up to three wire rope hoists.
─ Input F3 serves in measuring the load of a third wire rope hoist.
─ A value can be entered for parameter 5.11 (gear ratio). If a value is entered for this, parameter 3.0 cannot be set.
─ This interlocking thus excludes an incorrect setting.
─ The load-controlled switching point at output TxD of the LIS-SV can be used.
─ Parameter 4.5 (setting for load-controlled switching point) can be used.
The LIS-SV uses the signal of the encoder and the gear ratio of the hoisting gear to calculate the hook travel distance, the maximum distance in the limit switch range and the current rotational frequency of the hoist motor. The gear ratio must be set on the machine.
|
| |
|
Cable speed |
|
Read off the type
designation at the type plate of the wire rope hoist.
Read off the cable
speed.
From this table, select
the gear ratio that matches the cable speed.
|
Cable speed | |||||
|
Hoist motor GM |
32 m/min at 50 Hz |
25 m/min at 50 Hz |
20 m/min at 50 Hz |
16 m/min at 50 Hz | |
|
800.4 |
50.01 |
63.49 |
77.77 |
98.16 | |
|
800.5 |
47.03 |
60.04 |
74.66 |
95.03 | |
|
1000.6 |
54.43 |
68.91 |
84.00 |
105.1 | |
|
1000.7 |
54.60 |
68.06 |
81.45 |
104.6 | |
|
2000.3 |
58.22 |
74.23 |
91.19 |
118.4 | |
|
3000.4 |
73.61 |
93.92 |
118.4 |
152.9 | |
|
5000.3 |
85.14 |
109.3 |
132.8 |
169.0 | |
|
5000.4 |
80.20 |
104.9 |
127.7 |
160.6 | |
|
6000.3 |
94.69 |
118.5 |
149.6 |
182.7 | |
|
7000.1 |
118.0 |
148.3 |
182.6 |
232.0 | |
Table: Gear ratios (numerical values) depending on hoist motor (lines) and cable speeds (columns) at 50 and 60 Hz.
|
| |
|
Enter button |
Arrow buttons |
Move the load hook out of
the limit switch range (up or down).
During parameter setting, the load hook must not be within the limit switch range.
Select parameter 5.11.
Press ENTER.
● The set value is displayed.
If the value is 0.00, the function is deactivated.
● Hold ENTER pressed.
● CODE is displayed.
Hold ENTER pressed.
|
| |
|
Enter button |
Arrow buttons |
Enter the code 1443.
Press ENTER briefly.
|
| |
|
Enter button |
Arrow buttons |
Set the value from the
table.
If the display ‘0.00’ cannot be changed, a value is set in parameter 3.0. In this case, set the value to zero first.
Press ENTER briefly.
Downloadable from the official project release page on Romhacking.net or the team's GitHub repository.
It utilizes a "Partner Unit" system and "Tactical Commands" that provide passive buffs to the entire fleet based on chosen sub-commanders.
Unlike other entries, BX features a system where specific characters (like Flit from Gundam AGE ) provide global buffs that level up as you destroy enemies during a stage.
Using LayeredFS is the safest method. It does not modify your original game file permanently.
( Macross 30: Voices across the Galaxy , Macross Frontier ) Mazinger Edition Z: The Impact! super robot taisen bx english patch
The community relies on a highly detailed, text-and-screenshot narrative project:
In the meantime, the game remains completely playable for Japanese-proficient fans and for those who use the available menu patches and translation guides to bridge the language gap. The search for a true English patch for Super Robot Taisen BX continues, and the community waits with bated breath.
Comprehensive English guides on platforms like the Akurasu Wiki and Neoseeker provide translations for all menus, spirit commands, unit abilities, and mission objectives. How to Play SRW BX in English
It's a complete line by line translation of Super Robot Wars BX's story and DLCs. It may not be perfect or a proper patch, but it' Reddit·r/Super_Robot_Wars Super Robot Wars BX - PV1 (English Subs) Downloadable from the official project release page on
If you own a 3DS or a decent PC, and you have a legal copy of the game, applying this patch is a weekend project that pays off with 50+ hours of premium mecha strategy. The fan translation scene has once again proven that no game should be lost to a language barrier.
BX utilizes a duo-unit system. You pair two giant robots into a single squad. This allows for devastating combination attacks. It also lets slower mechs pair with faster ones to cross the battlefield quickly. Incredible Sprite Animations
The Super Robot Taisen BX English patch breathes new life into a handheld masterpiece. By following this guide, you can fully experience the deep strategic gameplay and massive crossover narrative without any language barriers. If you want to get started with the setup, let me know:
Since Super Robot Wars games share a consistent UI across most entries, many players use the translation script alongside static menu guides. Using LayeredFS is the safest method
is famous among mecha fans for its incredible roster, featuring several entries making their absolute debut in the franchise. Notable featured series include: Mobile Suit Gundam AGE SD Gundam Gaiden Panzer World Galient Giant Gorg Macross 30: Voices Across the Galaxy The King of Braves GaoGaiGar Mazinkaiser SKL 🔗 Further Exploration Learn more about the series list and flowcharts on the Akurasu Wiki
: A decrypted .3ds or .cia file of the Japanese version of the game. Step-by-Step Installation Guide
What sets SRW BX apart from other entries in the series is its unique, highly experimental roster. It successfully bridges generational gaps by combining classic 1970s super robots with modern 2010s real robot series. The official roster includes: (Making its mainline debut)
If you are using a Nintendo 3DS console with custom firmware (CFW), the installation process is designed to be simple:
The auxiliary fan of the hoist motor continues to run for several minutes after the lifting or lowering. This ensures that the hoist motor is adequately cooled even at slow lifting speeds. The run-on time can be adjusted.
|
| |
|
Enter button |
Arrow buttons |
Move the load hook out of
the limit switch range (up or down).
During parameter setting, the load hook must not be within the limit switch range.
Select parameter 5.14.
Press ENTER.
● The set value is displayed.
|
| |
|
Enter button |
|
Set the value to between 3
and 10 minutes using the arrow buttons.
Press ENTER.